I have some comments as follows:1. About 100% steel connection details sections:-AGC will calculate and return the worksheet you according to EC2 for precast columns, wall.-The measures South Korea will use MIG welding using MAG, CO2 will not alter the nature and intensity of steel. AGC will provide the South Korean measures for ICICI.-Location of connect beam length the AGC was calculated according to EC2 kernel of anpha6 = 1.5 and choose 56 d is eligible connection at the location good pull. (Image below). 2. The tunnel section design-The content presentation and calculation load drawings highlighted the load, the load combination factor. However, the computational models to test the intensity of SD390 steel and ensure progress (November 28, 2016) is not possible.AGC ICICI proposed providing more model files (ETABS...) and the tables of the appendix to part calculates the check is quick.